Parameters and Programming 5-7
36 [Base Voltage]
Set value to rated nameplate voltage of motor.
20/460 for
460V units
&
20/230 for
230V units
1 Volt
460 for
460V units
&
230 for
230V units
37 [Maximum Voltage]
Sets the highest voltage that the drive will output. P37 - [Maximum Voltage] must
be greater than or equal to P36 - [Base Voltage].
20/510 for
460V units
&
20/255 for
230V units
1 Volt
460 for
460V units
&
230 for
230V units
38 [Boost Select]
Sets the boost voltage and redefines the Volts per Hz curve. Settings 0-8 can
provide increased torque at low frequency. Settings 9 – 12 are used to reduce
energy consumption.
0/12 Numeric
Value
2
39 [Skip Frequency]
Works in conjunction with P40 - [Skip Frequency Band] creating a range of
frequencies at which the drive will not operate continuously.
0/240 1 Hz 240 Hz
40 [Skip Frequency Band]
Determines the band around the P39 - [Skip Frequency] parameter. The actual
band width will be 2 times P40 - [Skip Frequency Band] - 1/2 the band above and
1/2 the band below. A value of zero will disable the skip frequency.
0/30 1 Hz 0 Hz
Program Group
No. Parameter Name/Description
Min./Max.
Range
Units
Factory
Default
% [Base Frequency]
% [Base Voltage]
100
50
1/2 Base Volts
1/2
Base Freq.
9
10
11
12
0 50 100
1
8
See
S
ettings 1-8
Setting Boost Voltage
(% of [Base Voltage])
0
1
2
3
4
5
6
7
8
0
2.5
5.0
7.5
10.0
12.5
15.0
17.5
20.0
Setting Fan/Pump Curves
9
10
11
12
45.0
40.0
35.0
30.0
Break Point Voltages in percent of [Base Voltage]
tuptuO
ycneuqerF
rellortnoC
Frequency
Time
Skip
Frequency
Setting
Command
Frequency
2 x P40
[Skip Freq Band]
Setting