User Manual
POINT I/O Digital and Analog Modules and
POINTBlock I/O Modules
Catalog Numbers
1734-IA2, 1734-IM4, 1734-IB2, 1734-IB4, 1734-IB8, 1734-IB4D, 1734-IM2, 1734-IM4, 1734-
IV2, 1734-IV4, 1734-IV8, 1734-OA2, 1734-OA4, 1734-OB2, 1734-OB2EP, 1734-IV8, 1734-OA2, 1734-OA4, 1734-
OB2, 1734-OB2EP, 1734-OB2E, 1734-OB4, 1734-OB4E, 1734-OB8, 1734-OB8E, 1734-OV2E, 1734-OV4E,
1734-OV8E, 1734-OW2, 1734-OW4, 1734-OX2, 1734-IE2C, 1734-IE2V, 1734-OE2C, 1734-OE2V, 1734D-IA16,
1734D-IA8XOA8, 1734D-IA8XOW8, 1734D-IB16, 1734D-IB8XOB8, 1734D-IB8XOW8
Zobrazit stránku 0
1 2 3 4 5 6 ... 220 221

Shrnutí obsahu

Strany 1 - POINTBlock I/O Modules

User ManualPOINT I/O Digital and Analog Modules and POINTBlock I/O ModulesCatalog Numbers 1734-IA2, 1734-IM4, 1734-IB2, 1734-IB4, 1734-IB8, 1734-IB4D

Strany 2 - Important User Information

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xviii 1734-IA2 and 1734-IA4 120 V AC Input Modules . . . . . . . . . . . . . 531

Strany 3 - Summary of Changes

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013102 POINT I/O Module DataAnalog Input ModulesThe 1734-IE2C Analog Input Module is a

Strany 4

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 103DataThe1734-IE2C module operates in unipolar mode only; th

Strany 5 - Who Should Use This

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013104 POINT I/O Module DataScalingSelect scaling for each channel by making the selec

Strany 6 - Additional Resources

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 105• Calibration Mode Bit - This bit (Channel Status Bit 1) i

Strany 7

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013106 POINT I/O Module DataAlarm DisableThis function disables all channel alarms and

Strany 8

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 107• 60 Hz - 100 ms update rate• 250 Hz - 24 ms update rate•

Strany 9 - Table of Contents

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013108 POINT I/O Module DataChannel Indicator Behavior See the table for a listing of

Strany 10

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 109The 1734-OE2V module:• consumes 4 bytes of data (scanner R

Strany 11 - Chapter 3

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013110 POINT I/O Module DataOperational ModesThe 1734-OE2C module has these modes:• 0…

Strany 12 - POINT I/O Module Data

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 111Since scalers have no restrictions, use care when configur

Strany 13 - Indicators

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013 xixChapter 3Install POINTBlock I/O ModulesAbout This Chapter . . . . . . . . . . .

Strany 14 - Mounting Dimensions

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013112 POINT I/O Module DataChannel Status can be read individually using RSNetWorx so

Strany 15 - xxiii

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 113clamped. The clamps are absolute. Regardless of what is s

Strany 16

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013114 POINT I/O Module DataPOINTBlock I/O ModulesMount these 1734D input/output modul

Strany 17 - About the Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 115I/O messages are sent to (consumed) and received from (pro

Strany 18 - Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013116 POINT I/O Module DataThe 1734D-IA8XOA8 module produces one byte of input data (

Strany 19 - Analog Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 117Default Data for the 1734D-IB16 ModuleMessage Size: 2 byte

Strany 20

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013118 POINT I/O Module DataNotes:

Strany 21 - Miscellaneous Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 5Calibrate Your Analog ModulesAbout This ChapterRead this chapter for information

Strany 22 - 6 About the Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013120 Calibrate Your Analog ModulesTools Required to Calibrate Your Analog ModulesTo

Strany 23 - Install POINT I/O Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 121Calibrate the Analog Current Input ModuleTo calibr

Strany 24 - Explosion Hazard

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xx Chapter 4POINT I/O Module DataAbout This Chapter. . . . . . . . . . . . . . . .

Strany 25 - Assembly

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013122 Calibrate Your Analog ModulesThe EDS editor asks you if you want to upload the

Strany 26

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 1237. Click Calibration Channel Set to bring up chann

Strany 27 - Install an I/O Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013124 Calibrate Your Analog Modules11. From the Device Parameters dialog, click the D

Strany 28 - Terminal Block

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 125Calibrate the Analog Current Output ModuleTo calib

Strany 29 - Remove a Mounting Base

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013126 Calibrate Your Analog Modules2. From the EDS editor dialog, click Upload.3. Cli

Strany 30 - Wiring Digital Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 1277. Click Calibration Channel Sel to bring up chann

Strany 31

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013128 Calibrate Your Analog Modules10. Enter the value shown on your DVM for the Chan

Strany 32 - DeviceNet

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 12915. From the Device Parameters dialog, click Apply

Strany 33

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013130 Calibrate Your Analog ModulesCalibrate the Analog Voltage Input ModuleTo calibr

Strany 34 - 1734-IB4D Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 1313. From the EDS Editor dialog, click Upload.4. Fro

Strany 35

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013 xxiChapter 5Calibrate Your Analog ModulesAbout This Chapter . . . . . . . . . . .

Strany 36

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013132 Calibrate Your Analog ModulesBoth channel status indicators turn off.8. Apply 0

Strany 37

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 13314. Repeat these steps to calibrate the other chan

Strany 38 - V = Supply

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013134 Calibrate Your Analog Modules1. Double-click the icon to bring up the General p

Strany 39

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 1354. Select your channel(s). 5. Click Calibration Co

Strany 40

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013136 Calibrate Your Analog ModulesThe selected channel status indicator blinks green

Strany 41

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Calibrate Your Analog Modules 13712. Enter the value shown on the DVM onto your dia

Strany 42 - Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013138 Calibrate Your Analog Modules If calibration was accomplished, the Cal Status

Strany 43

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 6Troubleshoot with the IndicatorsAbout This ChapterRead this chapter for informati

Strany 44 - AC Power Bus

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013140 Troubleshoot with the IndicatorsNetwork and Module Status IndicationsThe networ

Strany 45 - 01 01 0101 01010101

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 141Troubleshoot Digital Modules The I/O status ind

Strany 46

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xxii Appendix ADefault Data MapsAbout This Appendix . . . . . . . . . . . . . . . .

Strany 47

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013142 Troubleshoot with the Indicators1734-OB2E, 1734-OB4E, and 1734-OB8E Source Outp

Strany 48

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 1431734-OB2EP Protected Output Module1734-IV2, 173

Strany 49

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013144 Troubleshoot with the Indicators1734-OV2E, 1734-OV4E, and 1734-OV8E Protected

Strany 50 - 01 01 01

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 1451734-OX2 Relay Output Module1734-IA2 and 1734-I

Strany 51

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013146 Troubleshoot with the Indicators1734-OA2 and 1734-OA4 120/220V AC Output Module

Strany 52

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 147Troubleshoot Analog ModulesEach analog module h

Strany 53

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013148 Troubleshoot with the Indicators1734-IE2V Analog Voltage Input Module 1734-OE2V

Strany 54

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 149Troubleshoot I/O Communication Modules The stat

Strany 55

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013150 Troubleshoot with the Indicators1734-ADN (X) DeviceNet AdapterIndication Probab

Strany 56

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 151Subnet and POINTBus StatusOff Device is not onl

Strany 57

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013 xxiiiAppendix CConfigure POINT I/O Modules in RSLogix 5000 SoftwareAbout This Appe

Strany 58 - Wiring Analog Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013152 Troubleshoot with the Indicators1734-ACNR ControlNet AdapterModuleStatusPointBu

Strany 59 - 11 3 5 7

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 153Indication Probable Cause Recommended ActionPOI

Strany 60

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013154 Troubleshoot with the Indicators1734-APB PROFIBUS AdapterIndication Probable Ca

Strany 61

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 155Flashing red 1 Hz - Check_Configuration telegra

Strany 62 - Wiring Power Distribution

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013156 Troubleshoot with the Indicators1734-AENT EtherNet/IP AdapterSystem PowerField

Strany 63 - C = Common V = Supply

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Troubleshoot with the Indicators 157Indication Probable Cause Recommended ActionSys

Strany 64

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013158 Troubleshoot with the IndicatorsNotes:

Strany 65

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Appendix ADefault Data MapsAbout This AppendixRead this appendix for a list of default dat

Strany 66

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013166 Default Data MapsDigital Module Default Data Maps I/O messages are sent to (con

Strany 67 - 12/24V DC Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Default Data Maps 167Produce 1 (Rx) SC 3 SC 2 SC 1 SC 0 OW 3 OW 2 OW 1 OW 0Consume

Strany 68 - IMPORTANT

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xxiv Notes:

Strany 69 - 120/240V AC Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013168 Default Data Maps1734-IV2 Source Input ModuleMessage Size: 1 Byte1734-IV4 Sourc

Strany 70 - 0101 0101

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Default Data Maps 1691734-IA2 Input Module Message Size: 1 Byte1734-IA4 Input Modu

Strany 71

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013170 Default Data Maps1734-OA2 Output ModuleMessage Size: 1 Byte 1734-OA4 Output Mod

Strany 72 - Sink Input Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Default Data Maps 171Message Size: 1 Byte1734-OB8E, 1734-OB8 Electronically Protect

Strany 73

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013172 Default Data Maps1734-OV2E Output ModuleMessage Size: 1 ByteMessage Size: 1 Byt

Strany 74

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Default Data Maps 173Message Size: 1 Byte1734-OW2 Relay Sink/Source Output ModuleMe

Strany 75 - Wiring POINTBlock

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013174 Default Data MapsAnalog Module Default Data Maps I/O messages are sent to (cons

Strany 76 - RTB 0 RTB 1 RTB 2 RTB 3 RTB 4

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Default Data Maps 1751734-OE2C Analog Current Output ModuleMessage Size: 4 bytesMes

Strany 77 - Output Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013176 Default Data MapsNotes:

Strany 78 - DeviceNet Connector Wiring

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Appendix BMounting DimensionsAbout This AppendixRead this appendix for mounting dimensions

Strany 79

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 1About the ModulesAbout This ChapterThis chapter introduces POINT I/O and related

Strany 80

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013178 Mounting DimensionsPOINT I/O Module with a 1734-PDN Module See the figure for m

Strany 81

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Mounting Dimensions 179POINTBlock Module See the figure for mounting dimensions for

Strany 82 - Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013180 Mounting DimensionsNotes:

Strany 83 - Input Wiring Diagram

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Appendix CConfigure POINT I/O Modules in RSLogix 5000 SoftwareAbout This AppendixRead this

Strany 84

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013182 Configure POINT I/O Modules in RSLogix 5000 Software3. Choose the Connection ta

Strany 85

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 183About Fault/Program Action

Strany 86

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013184 Configure POINT I/O Modules in RSLogix 5000 SoftwareThe choices for connection

Strany 87

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 185– General – Connection– Fau

Strany 88

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013186 Configure POINT I/O Modules in RSLogix 5000 Software3. From the Configuration d

Strany 89

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 1871. From the General dialog,

Strany 90

Rockwell Automation Publication 1734-UM001E-EN-P - July 20132 About the ModulesInput ModulesFor input modules, DC inputs are 24V DC nominal, wi

Strany 91

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013188 Configure POINT I/O Modules in RSLogix 5000 Software• Click another tab at the

Strany 92

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 1892. From the Configuration d

Strany 93

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013190 Configure POINT I/O Modules in RSLogix 5000 Software• Auto RestartSee the figur

Strany 94

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 191Configure Analog ModulesTo

Strany 95 - Digital AC Input Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013192 Configure POINT I/O Modules in RSLogix 5000 SoftwareWhen you change entries for

Strany 96 - Digital Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 193You see a Configuration dia

Strany 97

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013194 Configure POINT I/O Modules in RSLogix 5000 Software• Click OK to save changes

Strany 98 - Digital AC Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 195a. Click a channel push but

Strany 99 - Relay Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013196 Configure POINT I/O Modules in RSLogix 5000 Software2. Check the Calibrate chec

Strany 100 - Analog Input Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 197You see the Calibration Com

Strany 101 - Communicate with Your Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013About the Modules 3The 1734-OA2 and 1734-OA4 AC output modules have sourcing output

Strany 102 - Channel Status

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013198 Configure POINT I/O Modules in RSLogix 5000 SoftwareSee the figure that shows c

Strany 103 - Latch Alarms

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 1991. From the top of the Gene

Strany 104 - Update Rate

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013200 Configure POINT I/O Modules in RSLogix 5000 SoftwareYou see a Fault/Program Act

Strany 105 - Range Status

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 201You see the Calibration dia

Strany 106 - Analog Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013202 Configure POINT I/O Modules in RSLogix 5000 SoftwareYou see a Low Value dialog.

Strany 107

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules in RSLogix 5000 Software 203If calibration fails, the R

Strany 108 - Scaling

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013204 Configure POINT I/O Modules in RSLogix 5000 SoftwareNotes:

Strany 109

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Appendix DConfigure POINT I/O Modules for DeviceNet NetworksAbout This AppendixRead this a

Strany 110 - Low and High Clamps

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013206 Configure POINT I/O Modules for DeviceNet Networksdevice has been commissioned

Strany 111 - Channel Indicators

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 207For example, assume you have

Strany 112

Important User InformationSolid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines

Strany 113

Rockwell Automation Publication 1734-UM001E-EN-P - July 20134 About the Modules– Channel 1 Status (1 byte)• Output modules consume 4 bytes of d

Strany 114

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013208 Configure POINT I/O Modules for DeviceNet NetworksA dialog similar to the follo

Strany 115 - Message Size: 2 bytes

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 209The Group’s pull-down include

Strany 116

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013210 Configure POINT I/O Modules for DeviceNet Networksthe network, and you are prev

Strany 117 - Calibrate Your Analog Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 211Configure Output ModulesTo co

Strany 118 - Your Analog Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013212 Configure POINT I/O Modules for DeviceNet Networks• I/O output status• Reset se

Strany 119 - Current Input Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 213See the figures for dialogs f

Strany 120 - This is the group

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013214 Configure POINT I/O Modules for DeviceNet NetworksSee the figure for a dialog f

Strany 121 - Leave on single

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 215See the figure for a dialog f

Strany 122

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013216 Configure POINT I/O Modules for DeviceNet Networks3. From the Device Parameters

Strany 123 - 01 01 01 01

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 217• Autobaud - Enable/Disable

Strany 124 - Group pull-down

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013About the Modules 5• Low and high clamps can be set individually or on a channel ba

Strany 125

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013218 Configure POINT I/O Modules for DeviceNet Networks4. From the Device Parameters

Strany 126

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 219Configure Analog Modules Usin

Strany 127

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013220 Configure POINT I/O Modules for DeviceNet Networks An EDS Editor dialog appears

Strany 128

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 221To configure the analog outpu

Strany 129

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013222 Configure POINT I/O Modules for DeviceNet Networks5. From the Device Parameters

Strany 130

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Configure POINT I/O Modules for DeviceNet Networks 223• Go to Fault Value 7. For En

Strany 131

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013224 Configure POINT I/O Modules for DeviceNet NetworksWith current or voltage modul

Strany 132 - Click Calibration

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013IndexNumerics1734D-IA16 moduleabout 14wire 871734D-IA8XOA8 moduleabout 14wire 811734D-IA8X

Strany 133

226 Rockwell Automation Publication 1734-UM001E-EN-P - July 2013226 Index1734-OB2EP moduleabout 13default data map 167troubleshoot 142wire 3717

Strany 134 - (-10.1234 in the example)

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013 227 Indexcommissioningnodes 211tool 212configure analog modulesusing RSLogix 5000 sof

Strany 135

Rockwell Automation Publication 1734-UM001E-EN-P - July 20136 About the ModulesNotes:

Strany 136

228 Rockwell Automation Publication 1734-UM001E-EN-P - July 2013228 Indexremove a mounting base 25RSNetWorx software 206for DeviceNet node comm

Strany 137 - About This Chapter

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400Rockwell Automation Publication 17

Strany 138

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 2Install POINT I/O ModulesAbout This ChapterRead this chapter for installation and

Strany 139 - Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 20138 Install POINT I/O ModulesExplosion HazardPrevent Electrostatic DischargeATTENTION

Strany 140 - 1734-OB8

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 9Install the Mounting Base AssemblyThe 1734-TB, 1734-TBS,

Strany 141 - 1734-IV8

Rockwell Automation Publication 1734-UM001E-EN-P - July 201310 Install POINT I/O Modules1. Position the mounting base (wiring base assembly) ve

Strany 142 - 1734-OV2E 1734-OV4E 1734-OV8E

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 11The mounting base snaps into place.4. To remove the mou

Strany 143 - 1734-OX2 Relay Output Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 201312 Install POINT I/O Modules2. Make certain the DIN-rail locking screw is in the ho

Strany 144 - 1734-IM4

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 132. Rotate the terminal block into the mounting base unt

Strany 145 - Troubleshoot Analog

Publication 1734-UM001E-EN-P - July 2013Summary of ChangesThis publication contains new and revised information not in the last release.New Informatio

Strany 146

Rockwell Automation Publication 1734-UM001E-EN-P - July 201314 Install POINT I/O ModulesWiring Digital ModulesRefer to this section to wire dig

Strany 147 - Communication Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 151734-IB4 Module Wiring Diagram1734-IB8 Module Wiring Di

Strany 148 - 1734-ADNX DeviceNet Adapter

Rockwell Automation Publication 1734-UM001E-EN-P - July 201316 Install POINT I/O ModulesExample of Wiring - 1734-IB8 Module Using 2-Wire Proxim

Strany 149

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 17Example of Wiring - 1734-IB8 Module Using 3-wire Proxim

Strany 150 - • Firmware fatal error

Rockwell Automation Publication 1734-UM001E-EN-P - July 201318 Install POINT I/O Modules1734-IB4D Modules 1734-IB4D Module Wiring Diagram Ch

Strany 151

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 191734-IV2, 1734-IV4, and 1734-IV8 Source Input Modules17

Strany 152 - 1734-APB PROFIBUS Adapter

Rockwell Automation Publication 1734-UM001E-EN-P - July 201320 Install POINT I/O Modules1734-IV4 Module Wiring Diagram1734-IV8 Module Wiring Di

Strany 153 - • No power supplied

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 211734-OB2E, 1734-OB4E, 1734-OB8E, 1734-OB2, 1734-OB4, an

Strany 154 - 1734-AENT

Rockwell Automation Publication 1734-UM001E-EN-P - July 201322 Install POINT I/O Modules1734-OB2 and 1734-OB2E Module Wiring DiagramChannel Out

Strany 155

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 231734-OB4 and 1734-OB4E Module Wiring DiagramChannel Out

Strany 156

Publication 1734-UM001E-EN-P - July 2013iv Summary of ChangesNotes:

Strany 157

Rockwell Automation Publication 1734-UM001E-EN-P - July 201324 Install POINT I/O Modules1734-OB8 and 1734-OB8E Module Wiring Diagram Channel

Strany 158 - Data Maps

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 25 1734-OB2EP Protected Output Module1734-OB2EP DC Pro

Strany 159 - Where: OW = open wire

Rockwell Automation Publication 1734-UM001E-EN-P - July 201326 Install POINT I/O Modules1734-OW2 and 1734-OW4 Relay Output Modules1734-OW2 Modu

Strany 160 - 1734-IV8 Source Input Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 271734-OW2 Modules with Load Powered by External Power Wi

Strany 161 - 1734-IM4 Input Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 201328 Install POINT I/O ModulesRelay Modules Using AC Only 1B 32A 42B 63A 53B 7(1) Sup

Strany 162 - 1734-OA4 Output Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 29Relay Modules Using a 1734-FPD or 1734-EPAC Module to C

Strany 163 - Message Size: 1 Byte

Rockwell Automation Publication 1734-UM001E-EN-P - July 201330 Install POINT I/O Modules1734-OV2E, 1734-OV4E, and 1734-OV8E Sink Output Module

Strany 164 - 1734-OV8E Output Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 31DC Sink Output Module Cat. No. 1734-OV4E Wiring Diagram

Strany 165

Rockwell Automation Publication 1734-UM001E-EN-P - July 201332 Install POINT I/O Modules1734-OX2 2-relay Output Modules1734-OX2 Module with Loa

Strany 166 - Analog Module Default

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 331734-OX2 Modules with Load Powered by External Power Bu

Strany 167 - Message Size: 2 Bytes

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013PrefacePurpose of This ManualThis manual describes how to install, configure, and troubles

Strany 168 - 176 Default Data Maps

Rockwell Automation Publication 1734-UM001E-EN-P - July 201334 Install POINT I/O Modules01 01 0101 0100101101 01 01120V ACPDN OX2OX2PDN IB2 IB4

Strany 169

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 3501 0101 0101 0101 01 0101 01 0146124AENT01 0101 0101 01

Strany 170 - 1734-PDN Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 201336 Install POINT I/O Modules1734-IA2 and 1734-IA4 120 V AC Input Modules 01 01 010

Strany 171 - POINTBlock Module

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 37 1734-IA2 120 V AC Input Module Wiring Diagram1734-IA4

Strany 172

Rockwell Automation Publication 1734-UM001E-EN-P - July 201338 Install POINT I/O Modules1734-IM2 and 1734-IM4 220V AC Input Modules220VACInputM

Strany 173 - Software

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 39 1734-IM2 120V AC 2 Input Module Wiring DiagramChannel

Strany 174

Rockwell Automation Publication 1734-UM001E-EN-P - July 201340 Install POINT I/O Modules1734-OA2 and 1734- OA4 120/220V AC Output Modules120VAC

Strany 175 - Connection Type

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 41Channel Output TerminalCommon TerminalPower004115226337

Strany 176

Rockwell Automation Publication 1734-UM001E-EN-P - July 201342 Install POINT I/O ModulesWiring Analog Modules1734-IE2C Analog Current Input Mod

Strany 177

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 431734-IE2V Analog Voltage Input Module1734-IE2V Analog V

Strany 178

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xiv PrefaceAdditional ResourcesRefer to this table for a list of related 1734 produ

Strany 179

Rockwell Automation Publication 1734-UM001E-EN-P - July 201344 Install POINT I/O Modules1734-OE2C Analog Current Output Module1734-OE2C Analog

Strany 180

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 451734-OE2V Analog Voltage Output Module1734-OE2V Analog

Strany 181

Rockwell Automation Publication 1734-UM001E-EN-P - July 201346 Install POINT I/O ModulesWiring Power Distribution and Other Modules1734-PDN Com

Strany 182

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 47Wire the Communication Interface Module for AC Modules

Strany 183 - Configure Analog Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 201348 Install POINT I/O Modules1734-FPD Modules for 12/24V DC Wiring Diagram1734-FPD M

Strany 184

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 49This configuration changes the power bus voltage for AC

Strany 185

Rockwell Automation Publication 1734-UM001E-EN-P - July 201350 Install POINT I/O ModulesWiring Using a 1734-FPD Module to Create a New Analog P

Strany 186

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 5112/24V DC Wiring Diagram Example of Continuing PowerA

Strany 187

Rockwell Automation Publication 1734-UM001E-EN-P - July 201352 Install POINT I/O ModulesExample of Functional PartitioningExample of Logical Pa

Strany 188

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 531734-EPAC AC Expansion Power Supply120/240V AC Wiring D

Strany 189

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Preface xv8 AC Input/8 AC Relay Output Module Installation Instructions, publicatio

Strany 190

Rockwell Automation Publication 1734-UM001E-EN-P - July 201354 Install POINT I/O ModulesExample of Functional Partitioning ATTENTION: Use the

Strany 191

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 55Example of Logical Partitioning1734-ARM Address Reserve

Strany 192

Rockwell Automation Publication 1734-UM001E-EN-P - July 201356 Install POINT I/O Modules1734-CTM and 1734-VTM Modules Sink Input Wiring Diagra

Strany 193

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINT I/O Modules 57Source Input Wiring DiagramSource Output Wiring Diagram

Strany 194

Rockwell Automation Publication 1734-UM001E-EN-P - July 201358 Install POINT I/O ModulesGeneral Purpose Wiring Diagram C = Common1734CTM1734VT

Strany 195

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 3Install POINTBlock I/O ModulesAbout This ChapterRead this chapter for information

Strany 196

Rockwell Automation Publication 1734-UM001E-EN-P - July 201378 Install POINTBlock I/O Modules8 Input/8 Output Module Wiring DiagramSink Input W

Strany 197 - Networks

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 79Output Wiring Diagram Outputs are electronically p

Strany 198

Rockwell Automation Publication 1734-UM001E-EN-P - July 201380 Install POINTBlock I/O ModulesLatch Mode FunctionalityTo reset an output, the re

Strany 199 - Configure Digital Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 811734D-IB8XOW8 POINTBlock 8 DC In/8 Relay Out Modul

Strany 200 - Configure Input Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013xvi PrefaceRTD and Isolated Thermocouple Input User Manual, publication1734-UM004De

Strany 201

Rockwell Automation Publication 1734-UM001E-EN-P - July 201382 Install POINTBlock I/O ModulesSink Input WiringChannel Input Terminal Common Vol

Strany 202

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 83Output Wiring Diagram (Load Powered by External Po

Strany 203 - Configure Output Modules

Rockwell Automation Publication 1734-UM001E-EN-P - July 201384 Install POINTBlock I/O Modules1734D-IA8XOA8 POINTBlock 8 AC In/8 AC Out Modules1

Strany 204

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 85Input Wiring DiagramChannel Input Terminal Return

Strany 205

Rockwell Automation Publication 1734-UM001E-EN-P - July 201386 Install POINTBlock I/O ModulesOutput Wiring DiagramDeviceNet Connector WiringCha

Strany 206

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 871734D-IA8XOW8 POINTBlock 8 AC In/8 Relay Out Modul

Strany 207

Rockwell Automation Publication 1734-UM001E-EN-P - July 201388 Install POINTBlock I/O ModulesInput Wiring DiagramChannel Input Terminal Return

Strany 208

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 89Output Wiring DiagramDeviceNet Connector WiringCha

Strany 209 - • Autobaud - Enable/Disable

Rockwell Automation Publication 1734-UM001E-EN-P - July 201390 Install POINTBlock I/O Modules1734D-IA16 POINTBlock 16 AC Input ModulesWire the

Strany 210

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 91Input Wiring Diagram ATTENTION: When connecting mo

Strany 211

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Table of ContentsPrefacePurpose of This Manual. . . . . . . . . . . . . . . . . . . . . .

Strany 212

Rockwell Automation Publication 1734-UM001E-EN-P - July 201392 Install POINTBlock I/O ModulesDeviceNet Connector Wiring1734D-IB16 POINTBlock 16

Strany 213

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Install POINTBlock I/O Modules 9316 DC Input Module Wiring Diagram Sink Input Wiri

Strany 214

Rockwell Automation Publication 1734-UM001E-EN-P - July 201394 Install POINTBlock I/O ModulesDeviceNet Connector Wiring62 4 673 5 7Remote Termi

Strany 215 - • Go to Fault Value

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013Chapter 4POINT I/O Module DataAbout This ChapterRead this chapter for information about mo

Strany 216

Rockwell Automation Publication 1734-UM001E-EN-P - July 201396 POINT I/O Module DataDefault Data Map for the 1734-IB2 and 1734-IV2 Input Module

Strany 217 - Numerics

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 97Digital AC Input ModulesThe 1734 digital AC input modules f

Strany 218 - 226 Index

Rockwell Automation Publication 1734-UM001E-EN-P - July 201398 POINT I/O Module DataThese POINT I/O modules produce one byte of input data (sca

Strany 219

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 99Default Data Map for 1734-OB2, 1734-OB2E, and 1734-OV2E Out

Strany 220 - 228 Index

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013100 POINT I/O Module DataDigital AC Output ModulesThe 1734-OA2 AC output module fea

Strany 221 - Documentation Feedback

Rockwell Automation Publication 1734-UM001E-EN-P - July 2013POINT I/O Module Data 101Relay Output ModulesThe relay output modules consist of 17