Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Configure POINT I/O Modules in RSLogix 5000 Software 183
About Fault/Program Action and Configuration Dialogs
You see Fault/Program Action and Configuration dialogs based on the module
and connection types. Refer to the following table.
Understand Data and Connection Formats
For digital modules, the choices for data format and connection type are as
follows.
Data Format - Integer
Connection Type
Data
Listen only
Listen only - rack optimization
Rack optimization
When you change entries for data format and connection type, note the
following:
You do not delete the existing module.
You do n o t create a new m o du l e .
You bring forward configuration data for the new settings.
Any configuration data you do not bring forward sets to the default value.
After you apply new settings for data format and connection, note the following:
This is the base configuration for the next change in connection and data
format settings.
You lose all configuration data from previous data formats.
For Module
Type
With
Connection Type
You See These Tabs
(1)
(1) You see tabs for General, Connection, and Module Info for all module and connection types.
Fault/Program Action Configuration
Input Data x
Listen Only
Listen Only - Rack
Optimization
Rack Optimization x
Output Data x x
Listen Only
Listen Only - Rack
Optimization
Rack Optimization x x