130 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 8 I/O Modules
Add Remote I/O to the I/O Configuration
If you are adding remote I/O, add the I/O modules to the backplane of the
remote communication module that is connected to the controller. To add a
remote I/O to the I/O Configuration folder in the Logix Designer application,
complete these steps.
1. Add a communication module to the backplane that contains the
controller.
2. Specify the communication module properties according to your network
configuration.
For more information about the communication module and network
properties, see the Additional Resources
section in the preface.
3. Right-click the communication network and choose New Module.
4. Add the remote communication module that you are using.