Allen-Bradley ControlLogix Uživatelský manuál Strana 164

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 212
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 163
164 Rockwell Automation Publication 1756-UM001O-EN-P - October 2014
Chapter 10 Develop Applications
Interrupt the Execution of Logic and Execute the Fault Handler
Dependent on your application, you can want an I/O connection error to cause
the Controller Fault Handler to execute. To do so, set the module property that
causes a major fault to result from an I/O connection error. The major fault
causes the execution of the Controller Fault Handler.
First, develop a routine in the Controller Fault Handler that can respond to I/O
connection faults. Then, in the Module Properties dialog box of the I/O module
or parent communication module, check Major Fault On Controller If
Connection Fails While in Run Mode.
Figure 41 - I/O Connection Fault Causes Major Fault
For more information about programming the Controller Fault Handler, see the
Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014
.
Parent Communication Module Properties
I/O Module Properties
Zobrazit stránku 163
1 2 ... 159 160 161 162 163 164 165 166 167 168 169 ... 211 212

Komentáře k této Příručce

Žádné komentáře