118 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
PowerFlex DC Drive
PowerFlex DC I/O Signal and Control Wiring
Eight (8) digital inputs, four (4) digital outputs, three (3) analog inputs, and two
(2) analog outputs are available on the standard I/O terminal blocks provided
with the drive. One digital input (1-8) must be configured for “Enable”.
Additional digital and analog I/O is available when using the optional I/O
Expansion circuit board. Refer to Appendix F - “Optional Analog and Digital I/
O Expansion Circuit Board”, in the PowerFlex Digital DC Drive User Manual,
publication 20P-UM001
, for more information. Also, you can use the optional
115V AC Converter circuit board to convert 115V AC digital input signals to
24V DC digital inputs signals to interface with the digital inputs on the standard
I/O terminal blocks. Refer to Appendix G - “Optional 115V AC to 24V DC I/O
Converter Circuit Board” in the PowerFlex Digital DC Drive User Manual,
publication 20P-UM001
, for more information. All I/O terminal blocks are
located on the control board.
Figure 92 - I/O Terminal Block Locations
Table 17 - I/O Terminal Block 1 Designations
Terminal Block 1
Terminal Block 3 Terminal Block 4
Terminal Block 2
No. Signal Description Factory Default Related Parameter
1 Analog Input 1 (+) Isolated
(1)
, bipolar, differential,
±10V / 0-20mA, or 4-20mA.
Important: 0-20mA or 4-20mA operation requires
that switch S9, S10, and S11 on the Control board
be in the “Off” position. Drive damage may occur if
the switch is not in the correct position based on
the type of input signal. Refer to “DIP Switch and
Jumper Settings” in the PowerFlex Digital DC Drive
User Manual, publication 20P-UM001
.
Max ±10V, Max 0.25mA.
1 “Speed Ref A” 70 [Anlg In1 Sel]
2 Analog Input 1 (–)
3 Analog Input 2 (+) 0 “Off” 75 [Anlg In2 Sel]
4 Analog Input 2 (–)
5 Analog Input 3 (+) 0 “Off” 80 [Anlg In3 Sel]
6 Analog Input 3 (–)
7 +10V Pot Reference 2-5k ohm load. Max ±10V, Max 10mA. – –
8 –10V Pot Reference
9 Pot Common For (+) and (–) 10V pot references. – –
10 PE ground PE ground to drive chassis. – –
(1) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.