176 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 2 Wiring Examples
Figure 123 - Two-wire Control with Preset Speeds
Run
Stop/CF
Speed Select 2
16
15
14
13
31
37
38
39
40
11
12
35
36
32
34
33
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Not Used
17
18
20
19
Not Used
+24V DC Supply
Digital Input Common
24V Supply Common
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Not Used
Digital Input Common
Not Used
Not Used
Not Used
PE Ground
Internal 0V (Grd)
PowerFlex DC
TB2
TB4
• Conguration
P133 [Digital In1 Sel] is kept at its default of “Stop/CF”.
P134 [Digital In2 Sel] = 5 “Run”
P137 [Digital In5 Sel] = 17 “Speed Sel 1”
P138 [Digital In6 Sel] = 18 “Speed Sel 2”
P44 [Speed Ref A]
P48 [Speed Ref B]
P155 [Preset Speed 2]
P156 [Preset Speed 3]
Note: If Digital Input 5 & 6 are open, then the drive uses
P44 [Speed Ref A] as it’s speed reference.
- Refer to the PowerFlex DC User Manual,
Publication 20-p-um001, for more details on wiring
examples, Digital Input conguration and Speed Reference
selection.
NOTE: If your drive utilizes 115 VAC Inputs, refer to the
PowerFlex DC user manual, Appendix G for details on the
115V AC to 24V DC I/O Converter Circuit Board.
Speed Select 1
22
21
20
19
18
17
15
14
13
1
7
8
9
10
11
12
23
24
5
6
2
4
3
27
26
25
30
29
28
FlexPak 3000 Regulator Board with I/O Expansion Card
16
Clear Fault
31
32
RUN/STOP by
user contact
64
63
62
61
60
59
57
56
55
38
44
50
51
52
53
54
65
66
42
43
39
41
40
69
68
67
Dig Out 1 Com
Dig Out 2
58
Unused
Freq In A
Freq In A (not)
Com
Freq Out A
Freq Out A (not)
Com
Anlg In 1
Anlg In 1 Com
Anlg In 2
Anlg In 2 Com
Anlg Out 1
Anlg Out 1 Com
Anlg Out 2
24V DC
Dig In 1
Dig In 2
24V DC
Dig In 3
Dig In 4
Dig In 5
24V Com
Dig Out 1
33
34
Anlg Out 2 Com
Dig Out 2 Com
10V DC
Gnd
Meter Out Com
Meter Out2
+24V
Run
(1)
Stop
(1)
Jog
Reverse / Forward
Auto / Man
+24VDC
Coast / Stop
(1)
Customer Interlock
(1)
Fault / Alarm Reset
+24V
Digital Input 0
(1)
Motor Thermostat
(1)
+24V
+24V Common
+10VDC (Isolated)
Analog Manual Reference (+)
Analog Manual Reference (-)
Auto Reference (+)
Auto Reference (-)
Tachometer Hi Range
Tachometer Lo Range
Tachometer Common
Meter Out1
Running (N.O.)
Alarm (N.O.)
No Fault (N.O.)
• Conguration
P117 = [Preset Speed 1]
P118 = [Preset Speed 2]
P119 = [Preset Speed 3]
(1) Require for initial startup and
operational checks. Voltage must be
present at these points during operation. In
other words, these terminals must be made.
If open, the drive will be ‘Not Ready’.
(2) RUN – Edge sensitive signal that
initiates a Run command (0 1 = Run). If
the Drive is Run, voltage may be applied to
the armature causing the motor to reach the
desired speed.
NOTE: Install the I/O Expansion
Board in the drive carrier using the (2)
pan head screws provided, then plug
the middle ribbon cable connector into
J1.
- Refer to the FlexPak 3000
Drive I/O Expansion Kit, Publication
fp3-in007, for more details.
Preset Speed A
Preset Speed B
Two-wire Control, Preset Speeds