56 Rockwell Automation Publication PFLEX-AP009A-EN-P - September 2012
Chapter 1 Drive Comparisons
1395 External Field Transformer Connections
Figure 22 - 1395 - All Drives
L1
L3
1...30 Hp, 230 VAC
2...60 Hp, 460 VAC
TB1
TB1
TB8
1
2
3
4
1
2
3
4
5
1
3
To field bridge
L1
L3
L1
L3
FU
FU
FU
FU
FU
FU
25 A
25 A
50 A
50 A
Series B
125...300 Hp, 230 VAC
250...600 Hp, 460 VAC
MKVA Series B
40...100 Hp, 230 VAC
75...200 Hp, 460 VAC
Series A
230V
230V
230V
Field transformer
secondary 460V
Field transformer
secondary 460V
Field transformer
secondary 460V
(2)
(2)
(2)
(2)
Sized to load
(1)
(1)
(1)
(1)
(1)
(1)
(1) The primary of the external field transformer requires branch circuit protection, to be fused with FRN
or FRS style fuses. Refer to NEC Code (and local codes) for sizing.
(2) The secondary of the external field transformer must be fused with semiconductor type fuses; type
FWH-25 or FWH-50 depending on drive Hp rating.
Sized to load
Sized to load